Cautions
Ds=KX (Ts
+ Tc + Tt + Tbm ) + Ddf Ds: Min. safe mounting
distance of optical screen sensor denotes the shortest
distance from detection area to danger area K: Manual
speed is usually set at 1.M. In practical example, it
denotes speed of operators hand moving to work point
from normal start state. Ts: Time for machine to stop
depressing in S. Tc: Time form control to braking
reaction of machine in S Tt: Time for the optical
screen sensor to react in S. Tbm: Time that the brake
needs in S. |
Min. safe mounting distance o
optical screen sensor
Ds=KX (Ts + Tc + Tt + Tbm ) +
DH DH=1.2m-(0.4H),the Min Dh is 0.8m H: Min.
distance from optical screen sensor detection area to
ground in m. Note: Horizontalmounting angle of optical
screen sensor shall be less than 30
Check
After mounting, shut off the center, bottom, edge and
top of detection area of the optical screen sensor with
the detected object, and meanwhile detect that whether
the output state of optical screen sensor is normal.
|
Min. safe distance for
horizontally installing light screen: Ds
DCautions GM series
optical screen senor only for indoor use. Optical
screen sensor, high voltage wire and power wire shall be
connected or piped separately, to avoid wrong action
due to high electric induction. To avoid occasions
such as full of corrosive gas, too much dust,
severe vibration, directly sprayed by water, oil or
medicament or direct sunlight. No separate notice for
any change of the information in the future
|